This product is manufactured according to GB 9330¡°plustic¡ªinsulated control cable¡±and enterprise standards.
Applicable scope
For system connection wire of control,signal,protection or measuring for rated voltage up to and including450/750V.
Using features
Rated voltageUo/U: 450/750V
Permissible Max. continuous operating temperature of conductor
PVC insulated:70¡æ ; XLPE insulated:90¡æ
Upon short circuit(Max. Duration time 5s) The Max temperature of conductor not higher than
PVC insulated: 160¡æ ; XLPE insulated:250¡æ .
Ambient temperature of installation not less than 0¡æ
Prefered Permissible bending radium:
For non-armoured cable, not less than 6 times of cable diamete; For armoured or copper-tape-screened cable, not less than 12 times of cable diameter; For screened ?exible cable, not less than 6 times of cable diameter.
2)The special types of fire-retardent,flame-resisting,low-fume and ow-halogan,low-fume and non-halogan as well as acid-alkali-proof for these cables may be supplied upon requests.